Descriere
AC Operation
| Supply system configuration | TN, TT, IT (PE) |
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Input voltage range | 110 V AC ... 240 V AC ±10 % (PN = 120 W) |
| 100 V AC ... 109 V AC -15 % ... +10 % (PN = 100 W) | |
| Typical national grid voltage | 120 V AC |
| 230 V AC | |
| Voltage type of supply voltage | AC |
| Inrush current | typ. 39 A (at 25 °C) |
| Inrush current integral (I2t) | typ. 0.7 A2s |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
| Mains buffering time | typ. 15 ms (120 V AC) |
| typ. 42 ms (230 V AC) | |
| Current consumption | max. 2 A |
| max. 1.5 A | |
| typ. 1.3 A (110 V AC (120 W)) | |
| typ. 0.6 A (240 V AC (120 W)) | |
| typ. 1.2 A (100 V AC (100 W)) | |
| typ. 1.1 A (109 V AC (100 W)) | |
| Protective circuit | Transient protection; Varistor |
| Switch-on time | typ. 1 s |
| Device mains fuse | 3.15 A internal (device protection), fast-blow |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Discharge current to PE | < 3.5 mA |
DC Operation
| Efficiency | typ. 88 % (120 V AC) |
| typ. 89 % (230 V AC) | |
| Nominal output voltage | 24 V DC |
| Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| Nominal output current (IN) | max. 5 A (PN = 120 W) |
| max. 4.16 A (PN = 100 W) | |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Crest factor | typ. 1.5 (120 V AC) |
| typ. 1.5 (230 V AC) | |
| Output power (PN) | 120 W (240 V AC) |
| 100 W (100 V AC) | |
| Connection in parallel | yes, for increasing power and redundancy with diode |
| Connection in series | yes, for increased output voltage |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
| Residual ripple | typ. 70 mVPP (with nominal values) |
| Control deviation | < 2 % (change in load, static 10 % ... 90 %) |
| < 4 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Rise time | < 2 s (UOut = 10 % ... 90 %) |
| Minimum no-load power dissipation | < 1 W (120 V AC) |
| Maximum no-load power dissipation | < 1 W (230 V AC) |
| Minimum nominal load power dissipation | < 20 W (120 V AC) |
| Power loss nominal load max. | < 16 W (230 V AC) |
| Integrated fuse protection | no |





Recenzii